Novus N320 Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Sensoren Novus N320 herunter. NOVUS N320 User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 2
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
ELECTRICAL WIRING
It is important to follow the recommendations below:
Signal wires should be installed in grounded conduits and away from power or
contactor wires.
The instrument should have its own power supply wires that should not be
shared with electrical motors, coils, contactors, etc.
Installing RC filters (47 R and 100 nF, series combination) is strongly
recommended at contactor coils or any other inductors.
System failure should always be taken into account when designing a control
panel to avoid irreversible damage to equipment or people.
WARRANTY
Warranty conditions are available on our web site www.novusautomation.com.
TEMPERATURE METER
N320
OPERATING MANUAL - V1.8x
Man 5001217
The N320 is a temperature meter that provides you in the frontal display the
measured temperature of the sensor connected to its terminals. The temperature
sensors available are NTC Thermistor, Pt100, Pt1000 and J, K, T type
thermocouple, with offset correction capability.
The features of a particular model (input sensor type, sensor range, mains supply,
etc) are identified by the label placed on the thermometer body.
SPECIFICATIONS
INPUT SENSOR: The input sensor type can be chosen form the 4 options below
(specified when placing the order):
NTC Thermistor, 10 k @ 25 °C; range: 50 to 120 °C (-58 to 248 °F);
Accuracy: 1.0 °C (1.1 °F), with original sensor;
Sensor interchangeability: 1 °C (1.35 °F). This error can be compensated by
the offset parameter in the temperature meter.
Pt100 ( = 385); Range: 50 to 300 °C (-58 to 572 °F);
Accuracy: 0.7 °C (1.3 °F); IEC-751.
Pt1000 ( = 385); Range: 200 to 530 °C (-328 to 986 °F); Accuracy: 0.7 °C (1. F);
J, K or T thermocouple (IEC-584):
Type J: Range: 0 to 600 °C (32 to 1112 °F); Accuracy: 3 °C (5.4 °F);
Type K: Range: -50 to 1000 °C (-58 to 1832 °F); Accuracy: 3 °C (5.4 °F);
Type T: Range: -50 to 400 °C (-58 to 752 °F); Accuracy: 3 °C (5.4 °F);
Note: In the temperature meter with NTC input, a 3 m-sensor cable is bundled
with the instrument. The cable can be extended up to 200 m.
WARM-UP: 15 minutes
MEASUREMENT RESOLUTION:
0.1: from 19.9º to 199.9º display units with NTC, Pt100 and Pt1000
1: elsewhere
POWER SUPPLY: 100~240 Vac (± 10 %) or 24 Vdc/ac (12~30 Vdc/ac)
Mains frequency: 50~60 Hz. Power consumption: 5 VA
Caution: check the power supply specification before energizing the temperature
meter.
DIMENSIONS: Width x Height x Depth: 74 x 32 x 75 mm
Panel cut-out: 70 x 29 mm; Weight: 100 g
ENVIRONMENT: Operating temperature: 0 to 40 °C (32 to 122 °F)
Storage temperature: -20 to 60 °C (-4 to 140 °F)
Relative humidity: 20 to 85 % non-condensing
CASE: Polycarbonate UL94 V-2; Protection: Front panel: IP65, Box: IP42
Suitable wiring: Up to 4.0 mm²
RS-485 digital communication; RTU MODBUS protocol (optional)
Serial interface not isolated from input circuitry.
Serial interface isolated from input circuitry, except in 24 V powered model.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - SPECIFICATIONS

ELECTRICAL WIRING It is important to follow the recommendations below: Signal wires should be installed in grounded conduits and away from power or

Seite 2 - Fig. 1 – N320 terminals

Fig. 1 below shows the temperature meter connections to sensor, mains and outputs. Fig. 1 – N320 terminals Pt100 with 3 conductors. Te

Kommentare zu diesen Handbüchern

Keine Kommentare