Controller N1200
NOVUS AUTOMATION 7 / 13
Output High
Limit
Upper limit for the control output - Maximum
percentage for
the control output when in
automatic mode and in PID. Typically configured
with 100 %. Default value: 100 %
Softstart
SoftStart Function –: Time in seconds during which
the controller limits the MV value progressively
from 0 to 100 %. It is enabled at power up or when
the control output is activated. If in doubt set zero
(zero value disables the Soft start function).
ALARM SETPOINT: Tripping point for alarm 1, 2, 3
and 4. Value that defines the point of activation for
the programmed alarms with the functions “
” or
“
”.
For the alarms configured with Differential type
functions, this parameter defines deviation (band).
Not used for the other alarm functions.
CYCLE OF PROGRAMS
Program time
base
Defines the time base that will be used by all Ramp
& Soak programs.
- Time basis in seconds;
- Time basis in minutes;
Program
number
Selects the ramp and soak profile program to be
edited/viewed. The sequence of parameters that
follows refer to this selected program. Total of 20
programs possible.
Program
Tolerance
Maximum admitted deviation of PV
SP. If exceeded, the program execution is suspended
(the internal timer freezes) until the deviation be
returns back within the defined tolerance.
The value 0 (zero) disables the function
(the
program progresses regardless of the difference
between PV and SP).
Program SP’s, 0 to 9: Group of 10 values of SP that
define the Ramp and Soak profile segments.
Segments durations
, 1 to 9: Defines the time of
duration, in second or minutes, of
the program being edited.
Program event
Alarms of Event, 1 to 9: Parameters that define
which alarms are to be activated during the
execution of a certain program segment. The alarms
chosen must have its function configured as “
.”
(See Table 3)
Link Program
Link Programs: Number of t
to be linked following the current program
can be linked together to produce larger programs
of up to 180 segments
.
0 – do not link to any other program.
CYCLE OF ALARMS:
FUNCTIONS OF ALARMS 1 to 4. Defines the
functions for the alarms among the options of the
Table 3.
BLOCK ALARM 1 TO 4: This function blocks the
alarms when the controller is energized.
- enables initial blocking
- inhibits initial blocking
When enabled, the alarm will not be active at
power-up, waiting for PV (Process Variable) to
reach a non-alarm situation. From this point on the
alarm will be free to actuate should a new alarm
situation occur.
ALARM HYSTERESIS: Defines the difference
between the value of PV at which the alarm is
triggered and the value at which it is turned off (in
engineering units).
Alarm Time t1
Defines the temporization time t1, in seconds, for
the alarms. Defines the temporization time t1, in
seconds, for the alarms time functions. The value 0
(zero) disables the function.
Refer to Table 4 for configuring this parameter
timed functions. The value 0 (zero) disables the
function.
Refer to Table 4 for configuring this parameter.
Alarm Time t2. Defines the temporization time t2,
in seconds, for the alarms time functions. The
value 0 (zero) disables the function. Refer to Table
4 for configuring this parameter
Flash
Allows visual signalization of an alarm occurrence
by flashing the indication of PV in the operation
level. The user chooses which alarms are to be
associated with this feature.
CYCLE OF SCALE
Type
INPUT TYPE: Selects the input signal type to be
connected to the process variable input. Refer to
Table 1 for the available options.
Filter
Digital Input Filter - Used to improve the stability of
the measured signal (PV). Adjustable between 0
and 20. In 0 (zero) it means filter turned off and 20
means maximum filter. The higher the filter value,
the slower is the response of the measured value.
Decimal Point
Selects the decimal point position to be viewed in
both PV and SP
.
Unit. Temperature indication in ºC or ºF:
Square Root
Square Root Function. Applies the quadratic
function on the input signal, within the limits
programmed in “
” and “
.”
Enables the Function
Does not enable the Function
The indication assumes the lower limit value when
the input signal is below 1 % of programmed span.
Parameter available for lineal inputs only.
Offset
SENSOR OFFSET: Offset value to be added to
the PV reading to compensate sensor error.
Default value: zero.
SP
Enables remote SP.
Enables the Function
Does not enable the Function
This parameter is not displayed when the remote
SP selection is defined by a Digital Input.
Remote SP
type
Defines the signal type for the remote SP.
current of 0-20 mA
current of 4-20 mA
voltage of 0-5 V
voltage of 0-10 V
Parameter displayed when remote SP is enabled.
Remote SP
Low Limit
REMOTE SETPOINT LOW LIMIT: used in
conjunction with the
rSxL, scales the remote SP
input defining the initial value in the remote SP
indication range.
Parameter displayed when remote SP is enabled.