7 – Digital input, Start/Stop control (“RvN
RvNRvN
RvN”: YES / no).
Closed = outputs enabled
Open = outputs disabled
8
88
8 – Invalid selection;
9
99
9 – Digital input, holds or allows R&S program progress.
Closed = enables program running;
Opened = holds program (the program resumes normal
operation when the contact is closed again. The
program resumes from the point is was prior to
the hold)
10
1010
10 – R&S program 1 selection. This option is useful when the user
wants to switch between the main setpoint and a second SP
defined in the ramp and soak program.
Closed = selects program 1;
Open = assumes the main setpoint
11
1111
11– Configures the I/O5 as an analog 0-20 mA control output.
12
1212
12– Configures the I/O5 as an analog 4-20 mA control output.
13
1313
13– Analog 0-20 mA retransmission of PV.
14
1414
14– Analog 4-20 mA retransmission of PV.
15
1515
15– Analog 0-20 mA retransmission of SP.
16
1616
16– Analog 4-20 mA retransmission of SP.
I/O 6 – Digital Input
0
00
0 - Disable the alarm;
6
66
6 - Digital input, manual/automatic selection:
Closed = manual control;
Open = automatic control
7
77
7 – Start/Stop control (“RvN
RvNRvN
RvN”: YES / no).
Closed = outputs enabled
Open = outputs disabled
8
88
8 – Invalid selection;
9
99
9 - Holds or allows R&S program progress.
Closed = enables program running;
Opened = holds the program (the program resumes normal
operation when the contact is closed again)
10
1010
10 – R&S program 1 selection. This option is useful when the user
wants to switch between the main setpoint and a second SP
defined in the ramp and soak program.
Closed = selects program 1;
Open = takes the main setpoint
Note: When a function is selected to operate through digital
input, the controller does not respond to the equivalent function
command given in the frontal keypad.
POTENTIOMETER INPUT
The potentiometer of valve position can be seen in the controller. It
must be 10 kΩ and connections must be as Figure 07 shows. The
potentiometer reading does not power the valve position for control
effects, it only informs the operator the valve current position. The
control action happens regardless of the potentiometer.
In order to visualize the potentiometer reading, the “Pot” parameter
must be enabled. When enabled (YES), the potentiometer position is
displayed on the prompt screen that shows the Manipulated Variable
(MV). When the potentiometer visualization is selected, the MV is not
shown anymore, and the percentage value of valve opening is shown
instead. The MV screen is the second prompt of the main cycle.
ALARM CONFIGURATION
The controller has 2 independent alarms. They can be programmed
to operate with nine different functions, represented in Table 3.
• Open sensor
It is activated whenever the input sensor is broken or disconnected.
• Event alarm
It activates alarm(s) in specific segments of the program. See item
7.2 in this manual.
• Resistance fail
Detects a heater broken condition, by monitoring the load current
when the control output is activated. This alarm function requires an
optional device (option 3). Details of the "resistance fail" option can
be found in a specific documentation that is sent with the product
when the option is purchased.
TYPE PROMPT
ACTION
Disabled
off
offoff
off
No active alarm. This output can be used as a digital
output to be set by the serial communication.
Sensor
Break
(input Error)
ierr
ierrierr
ierr
Alarm will be ON if PV sensor breaks, input signal is
out of range or Pt100 is shorted.
Event
Alarm
(ramp and
Soak)
rs
rsrs
rs
Can be activated at a specific segment of ramp and
soak program.
Detection
resistance
fail
rfail
rfailrfail
rfail
Detects a heater broken condition
Low Alarm
lo
lolo
lo
High Alarm
ki
kiki
ki
LOW
Differential
difl
difldifl
difl
PV
positive SPAn
negative SPAn
HIGH
Differential
difk
difkdifk
difk
PV
positive SPAn
PV
negative SPAn
Differential
dif
difdif
dif
SV - SPAn
positive SPAn
negative SPAn
Table 3 – Alarm functions
SPAn is meant to be the Alarm Setpoints “SPA1”, “SPA2”.
• Minimum value
It is activated when the measured value is below the value defined in
the alarm Setpoint.
• Maximum value
It is activated when the measured value is above the value defined in
the alarm Setpoint.
• Open sensor
It is activated whenever the input sensor is broken or disconnected.
• Event alarm
It activates alarm(s) in specific segments of the program. See item
7.2 in this manual.
• Resistance fail
Detects a heater broken condition, by monitoring the load current
when the control output is activated. This alarm function requires an
optional device (option 3). Details of the "resistance fail" option can
be found in a specific documentation that is sent with the product
when the option is purchased.
• Minimum value
It is activated when the measured value is below the value defined in
the alarm Setpoint.
• Maximum value
It is activated when the measured values is above the value defined in
the alarm Setpoint.
• Differential (or Band)
In this function, the parameters “SPA1
SPA1SPA1
SPA1”, “SPA2
SPA2SPA2
SPA2” represent the PV
deviation as compared to the main SP.
In a positive deviation, the differential alarm will be triggered when
the measured value is out of the range defined in:
( SP – Deviation) and (SP + Deviation)
In a negative deviation, the differential alarm will be triggered when
the measured value is within the range defined above.