NOVUS AUTOMATION 1/11
Controller
N1100
UNIVERSAL CONTROLLER
INSTRUCTIONS MANUAL V4.0x
SAFETY ALERTS
The symbols below are used on the equipment and throughout this
document to draw the user’s attention to important operational and
safety information.
CAUTION:
Read complete instructions prior to
installation and operation of the
unit.
CAUTION OR WARNING:
Electrical shock hazard.
All safety related instructions that appear in the manual must be
observed to ensure personal safety and to prevent damage to either
the instrument or the system. If the instrument is used in a manner not
specified by the manufacturer, the protection provided by the
equipment may be impaired.
PRESENTATION
The N1100 is an extraordinarily versatile process controller. It holds
in one single instrument all the main features needed for the vast
majority of industrial processes. It accepts in a single model virtually
all the sensors and signals used in the industry and provides the
main output types required for the operation of diverse processes.
The configuration can be performed directly on the controller or through
the USB interface. The NConfig software (free) is the configuration
management tool. Connected to the USB of a Windows computer, the
controller is recognized as a serial communications port (COM) running
with a Modbus RTU protocol.
Through the USB interface, even if disconnected from the power
supply, the configuration performed in a piece of equipment can be can
be saved in a file and repeated in other pieces of equipment that
require the same configuration.
It is important that the users read carefully this manual before using
the controller. Verify if the release of this manual matches the
instrument version (the firmware version is shown when the controller
is energized).
MAIN CHARACTERISTICS
Multi-sensor universal input (sensors and standard signals);
Protection for open sensor in any condition;
Relay, 4-20 mA and logic pulse control outputs all available in the
standard model;
Self-tuning of PID parameters;
Automatic / Manual function with “bumpless” transfer;
Four modes of independents alarms, with functions of minimum,
maximum, differential (deviation), open sensor and event;
Timer functions that can be associated to the alarms;
Retransmission of PV or SP in 0-20 mA or 4-20 mA;
Input for remote setpoint;
Digital input with 5 functions;
Programmable soft-start;
7 setpoint profile programs with 7 segments each, with the ability
to be linked together for a total of 49 segments;
Password for parameters protection;
Universal power supply.
CONFIGURATION / FEATURES
Select the input type (in parameter
tYPE
”) from Table 1 below
TYPE CODE
CHARACTERISTICS /
RANGE OF MEASUREMENT
J
Tc j
Range: -110 to950 ºC (-166to 1742 ºF)
K
Tc k
Range: -150 to 1370 ºC (-238to 2498 ºF)
T
Tc t
Range: -160 to 400 ºC (-256to 752 ºF)
N
Tc n
Range: -270 to 1300 ºC (-454to 2372 ºF)
R
Tc r
Range: -50to 1760 ºC (-58to 3200 ºF)
S
Tc s
Range: -50to 1760 ºC (-58to 3200 ºF)
B
Tc b
Range: 400to 1800 ºC (752to 3272 ºF)
E
Tc e
Range: -90to 730ºC (-130to1346 ºF)
Pt100
Pt
Range: -200to850ºC (-328to1562ºF)
0–50 mV
L.0.50
Linear Signals
Programmable indication from-1999 to 9999
4-20 mA
L.4.20
0-5 Vdc
L0.5
4-20 mA
sqrt
4-20 mA input with Square Root extraction.
Programmable indication from-1999 to 9999
4-20 mA
NON
LINEAR
ln j
Non Linear Analog Signals
Indication range depends on the selected sensor
Ln k
ln t
ln n
ln r
ln s
ln b
ln E
Ln.Pt
Table 1Input types
Note: All input types are factory calibrated.
OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION
The controller input and output channels (I / O) can assume multiple
functions: control output, digital input, digital output, alarm output,
retransmission of PV and SP. These channels are identified as I / O
1, I / O 2, I / O 3, I / O 4 and I / O 5.
The basic controller model comes loaded with the following features:
I / O 1- output to Relay SPST-NA;
I / O 2- output to Relay SPST-NA;
I / O 5- current output, digital output, digital input;
Optionally, other features can be added, as shown under the item
Identification” in this manual:
- 3R: I / O3 with output to SPDT relay;
- DIO: I / O3 and I / O4 as digital input and output channels;
- 485: Serial Communication
Seitenansicht 0
1 2 3 4 5 6 ... 10 11

Inhaltsverzeichnis

Seite 1 - Controller

NOVUS AUTOMATION 1/11 Controller N1100 UNIVERSAL CONTROLLER – INSTRUCTIONS MANUAL – V4.0x SAFETY ALERTS The symbols below are used on the equipment

Seite 2 - NOVUS AUTOMATION 2/11

N1100 Controller NOVUS AUTOMATION 10/11 CALIBRATION OF THE INPUT All inputs are factory calibrated and recalibration should only be done by qualified

Seite 3 - (ramp and Soak)

N1100 Controller NOVUS AUTOMATION 11/11 All registers are 16 bit signed integers. Address Parameter Register Description 0000 Active SP Read: Act

Seite 4 - T/C, 0-50mV

N1100 Controller NOVUS AUTOMATION 2/11 The function code of each I/O can be selected among the options on Table 2. I/O TYPE I/O FUNCTION CODE - No fu

Seite 5 - OPERATION

N1100 Controller NOVUS AUTOMATION 3/11 PROMPT TYPE ACTION Off Disabled Output is not used as alarm. Ierr Sensor Break (input Error) Activated when t

Seite 6 - NOVUS AUTOMATION 6/11

N1100 Controller NOVUS AUTOMATION 4/11 USB INTERFACE The USB interface is used for CONFIGURING or MONITORING the controller. The NConfig software mus

Seite 7 - NOVUS AUTOMATION 7/11

N1100 Controller NOVUS AUTOMATION 5/11 Remote Setpoint Feature available in the controller's terminals 9 and 10. When the Remote SP input signal

Seite 8 - PROTECTION OF CONFIGURATION

N1100 Controller NOVUS AUTOMATION 6/11 DESCRIPTION OF THE PARAMETERS PV / SP indication - The upper display shows the current value of PV. The lower

Seite 9 - MAINTENANCE

N1100 Controller NOVUS AUTOMATION 7/11 CYCLE OF ALARMS Fva1 Fva2 Fva3 Fva4 Function Alarm Functions of Alarms. Defines the functions for the alarms a

Seite 10 - COMMUNICATION

N1100 Controller NOVUS AUTOMATION 8/11 rsL( Remote SP Low Calibration See section: MAINTENANCE / Input Calibration. Enter the value corresponding to

Seite 11 - SUPPORT AND MAINTENANCE

N1100 Controller NOVUS AUTOMATION 9/11 The master password is made up by the last three digits of the serial number of the controller added to the nu