NOVUS AUTOMATION 1 / 13
Controller N1200
UNIVERSAL CONTRO
LLER - INSTRUCTIONS MANUAL V2.0x
SAFETY ALERTS
The symbols below are used on the equipment and throughout this
document to draw the user’s attention to important operational and
safety information.
CAUTION:
Read the manual thoroughly
before installing and operating the
equipment.
CAUTION OR DANGER:
Electrical Shock Hazard
All safety related instructions that appear in the manual must be
observed to ensure personal safety and to prevent damage to either
the instrument or the system. If the instrument is used in a manner
not specified by the manufacturer, the protection provided by the
equipment may be impaired.
INTRODUCTION
The N1200 is an extraordinarily versatile process controller. It holds
in one single instrument all the main features needed for the vast
majority of industrial processes. It accepts in a single model virtually
all the sensors and signals used in the industry and provides the
main output types required for the operation of diverse processes.
The configuration can be performed directly on the controller or
through the USB interface. The NConfig software (free) is the
configuration management tool. Connected to the USB of a Windows
computer, the controller is recognized as a serial communications
port (COM) running with a Modbus RTU protocol.
Through the USB interface, even if disconnected from the power
supply, the configuration performed in a piece of equipment can be
can be saved in a file and repeated in other pieces of equipment that
require the same configuration.
It is important that the users read carefully this manual before using
the controller. Verify if the release of this manual matches the
instrument version (the firmware version is shown when the controller
is energized). The N1200 main characteristics are:
Multi-sensor universal input;
Protection for open sensor in any condition;
Relay, 4-20 mA and logic pulse control outputs all available in
the standard model;
Self-tuning of PID parameters;
Automatic / Manual function with “bumpless” transfer;
Four modes of independents alarms, with functions of minimum,
maximum, differential (deviation), open sensor and event;
Timer functions that can be associated to the alarms;
Retransmission of PV or SP in 0-20 mA or 4-20 mA;
Input for remote setpoint;
Digital input with 5 functions;
Programmable soft-start;
20 setpoint profile programs with 9 segments each, with the
ability to be linked together for a total of 180 segments;
Password for parameters protection;
Universal power supply.
CONFIGURATION / FEATURES
INPUT TYPE SELECTION
Select the input type (in parameter
tYPE
”) from Table 1 below.
TYPE
CODE
RANGE OF MEASUREMENT
J
Tc j
Range: -110 to 950 ºC (-166 to 1742 ºF)
K
Tc k
Range: -150 to 1370 ºC (-238 to 2498 ºF)
T
Tc t
Range: -160 to 400 ºC (-256 to 752 ºF)
N
Tc n
Range: -270 to 1300 ºC (-454 to 2372 ºF)
R
Tc r
Range: -50 to 1760 ºC (-58 to 3200 ºF)
S
Tc s
Range: -50 to 1760 ºC (-58 to 3200 ºF)
B
Tc b
Range: 400 to 1800 ºC (752 to 3272 ºF)
E
Tc e
Range: -90 to 730 ºC (-130 to 1346 ºF)
Pt100
Pt
Range: -200 to 850 ºC (-328 to 1562 ºF)
0-20 mA
L0.20
Linear Signals
Programmable indication from -1999 to 9999.
4-20 mA
L4.20
0–50 mV
L0.50
0-5 Vdc
L0.5
0-10 Vdc
L0.10
4-20 mA
NON
LINEAR
ln j
Non Linear Analog Signals
Indication range depends on the selected sensor
Ln k
ln t
ln n
ln r
ln s
ln b
ln E
Ln.Pt
Table 1 - Input types
Note: All input types are factory calibrated.
CONFIGURATION OF OUTPUTS, ALARMS AND DIGITAL INPUTS
The controller input and output channels (I / O) can assume multiple
functions: control output, digital input, digital output, alarm output,
retransmission of PV and SP. These channels are identified as I / O
1, I / O 2, I / O 3, I / O 4 and I / O 5.
The basic controller model comes loaded with the following features:
I / O 1- output to Relay SPST-NA;
I / O 2- output to Relay SPST-NA;
I / O 5- current output, digital output, digital input;
Optionally, other features can be added, as shown under the item
Identification” in this manual:
- 3R: I / O3 with output to SPDT relay;
- DIO: I / O3 and I / O4 as digital input and output channels;
- HBD: Heater break detect;
- 485: Serial Communication;
The function to be used in each channel of I/O is defined by the user
in accordance with the options shown in the Table 2.
Seitenansicht 0
1 2 3 4 5 6 ... 12 13

Inhaltsverzeichnis

Seite 1 - Controller N1200

NOVUS AUTOMATION 1 / 13 Controller N1200 UNIVERSAL CONTROLLER - INSTRUCTIONS MANUAL – V2.0x SAFETY ALERTS The symbols below are used on the equipme

Seite 2 - NOVUS AUTOMATION 2 / 13

Controller N1200 NOVUS AUTOMATION 10 / 13 The program tolerance defines the maximum deviation between PV and SP for the execution of the profile. If

Seite 3 - NOVUS AUTOMATION 3 / 13

Controller N1200 NOVUS AUTOMATION 11 / 13 The methods of automatic tuning and auto-adaptative tuning are appropriate for most of the industrial proc

Seite 4 - INSTALLATION / CONNECTIONS

Controller N1200 NOVUS AUTOMATION 12 / 13 REDUCED REGISTERS TABLE FOR SERIAL COMMUNICATION Communication Protocol The MOSBUS RTU slave is implement

Seite 5 - OPERATION

Controller N1200 NOVUS AUTOMATION 13 / 13 IDENTIFICATION N1200 - 3R - 485 - 24V A B C D A: Controller Model: N1200; B: Optional I/Os: Blank

Seite 6 - Loop break

Controller N1200 NOVUS AUTOMATION 2 / 13 FUNCTION OF I/O CODE TYPE OF I/O Without Function OFF Output Output of Alarm 1 A1 Output Output of Al

Seite 7 - NOVUS AUTOMATION 7 / 13

Controller N1200 NOVUS AUTOMATION 3 / 13 Using the Alarm 1 as example. • difk – Alarm of Maximum Differential Value Triggers when the value of PV

Seite 8

Controller N1200 NOVUS AUTOMATION 4 / 13 LBD - LOOP BREAK DETECTION ALARM The parameter defines a time interval, in minutes, within which the PV is

Seite 9 - PROGRAMS OF RAMP AND SOAK

Controller N1200 NOVUS AUTOMATION 5 / 13 Power Supply Connections Observe the power requirement for the unit. of required power supply Figure 2 –

Seite 10 - NOVUS AUTOMATION 10 / 13

Controller N1200 NOVUS AUTOMATION 6 / 13 In order to operate appropriately, the controller needs a configuration that is the definition of each one

Seite 11 - SERIAL COMMUNICATION

Controller N1200 NOVUS AUTOMATION 7 / 13 ovkl Output High Limit Upper limit for the control output - Maximum percentage for the control output whe

Seite 12 - SPECIFICATIONS

Controller N1200 NOVUS AUTOMATION 8 / 13 rskl Remote SP High Limit REMOTE SETPOINT HIGH LIMIT: defines the full scale indication of the Remote Setpo

Seite 13 - WARRANTY

NOVUS AUTOMATION 9 / 13 OPERATION CYCLE TUNING CYCLE PROGRAM CYCLE ALARM CYCLE CONFIGURATION CYCLE I/O CYCLE CALIBRATION CYCLE PV and SP atvn